Technical specifications
Dimensions:
1 additional standard location for Tyness
Connectors:
● 1 connector
● 8 terminals type AVX series 9276 (2/10° to 8/10° – 24 to 18 AWG)
● Rigid and flexible multi-strands
Number of inputs:
4 individually configurable inputs in 0-10V or 4-20mA with common mass in all of the Tyness.
Range of upstream signals:
Input 4-20 mA:
● <1 mA: signal lost from
● from1 mA to 20.5 mA: upstream signal
● >20.5 mA: out of range
● resolution 0.02 mA
● precision +- 100 uA
Input 0-10 V:
● from 0 V to 10.5 V: upstream signal
● >10.5 V: out of range
● resolution 10 mV
● precision +- 50 mV
Power supply:
By the TYNESS
Pinout of terminal block board:
Configuration of the inputs by the switches: