Cleaning the product
The cleaning of the product should be done with a dry, soft and lint-free cloth. Remove embedded deposits with a slightly damp cloth. Do not use any cleaner, alcohol or thinner.
Power supply of the sensor
The product must be powered by a 24VDC power supply and provide a minimum current of 1A. Connect the cable marked power supply of the product to this power supply. The red wire on the 24V and the black wire
Technical Specifications
POWER SUPPLY Voltage : 24VDC +-5% Power : 1,2W Power cable length : 1 meter (39,07 inches) Power supply voltage Fluctuation : ±5% of rated voltage POWER CURRENT MEASUREMENTS BY OPENING PINS Maximum allowable current/sections : 10mm/75A, 16mm/100A, 24mm/300A, 36mm/600A Measurable circuit
Measurements
The sensor enables to make different measurements. Here below are the wiring methods for each one. The technical characteristics are described at the bottom of the documentation. Measurements of current: The measurement of current is carried out by means of the
Product description
The TYNESS-FACTORY is a multifunctional LoRaWan radio sensor equipped with a remote omnidirectional magnetic antenna. It enables to perform : 3 current measurements by current clamps 2 temperature measurements by PT100 probes 2 digital input measurements 2 analog measurements 0-24V
Product installation
Positioning of the product The product must be positioned in a way that does not make it difficult to operate disconnector devices. The product must be installed in an indoor environment. Product dimensions Mounting on DIN rail The product must be installed on a 35mm
Homologations and compliances
FCC compliance statement This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause
Hazards and warnings
The manufacturer cannot be held responsible if the instructions in this manual are not followed. Any intervention on the product must be carried out by a qualified person. The product must be replaced by a qualified person. The device must be used in
Mesures
Le capteur permet d'effectuer différentes mesures. Voici ci-dessous les méthodes de câblage de chacune. Les caractéristiques techniques sont décrites en bas de documentation. Mesures de courant: La mesure de courant est effectuée au moyen des 3 pinces ampèremétriques ouvrante connectée au capteur