MBus protocol
Necessary prerequisites for compatibility between an Mbus meter and a Tyness opt Mbus card
Water meter :
The following information (VIF) must be found in the data available via a measurement data query.
VIF code (Value information field)
Description: volume
Coding: E001 0nnn
Range: 10(nnn-6) m3 which gives a unit ranging from 0.001l to 10000l
Calorimeter:
The following information (VIF) must be found in the data available via a measurement data query.
VIF code (Value information field)
Description : Energy (2 possibilités)
Coding: E000 0nnn
Range: 10(nnn-3) Wh which gives a unit ranging from 0.001Wh to 10000Wh
ou
Coding: E000 1nnn
Range: 10(nnn) J which gives a unit ranging from de 0.001kJ to 10000kJ
Description : volume
Coding: E001 0nnn
Range: 10(nnn-6) m3 which gives a unit ranging from 0.001l to 10000l
Description : Flow Temperature
Coding: E101 10nn
Range: 10(nn-3) °C which gives a unit ranging from 0.001°C to 1°C
Description : Return Temperature
Coding: E101 11nn
Range: 10(nn-3) °C which gives a unit ranging from 0.001°C to 1°C
Electricity meter:
The following information (VIF) must be found in the data available via a measurement data query.
VIF code (Value information field)
Description: Energy (2 possibilités)
Coding: E000 0nnn
Range: 10(nnn-3) Wh which gives a unit ranging from 0.001Wh to 10000Wh
ou
Coding: E000 1nnn
Range: 10(nnn) J which gives a unit ranging from 0.001kJ to 10000kJ
The following DIF codes are compatible with the Tyness opt Mbus card:
8 | 0001 | 8 Bit Integer |
16 | 0010 | 16 Bit Integer |
24 | 0011 | 24 Bit Integer |
32 | 0100 | 32 Bit Integer |
32 / N | 0101 | 32 Bit Real |
48 | 0110 | 48 Bit Integer |
64 | 0111 | 64 Bit Integer |