Homologations et conformités
EMC EN 61000-6-2 : Immunity for industrial environment EN 61000-6-3 : Emission for residential environment EN 55022 : IT equipment immunity Radio EN 30022 Safety EN 61010 : IT equipment
Références
SQUID : SQUID V2 in LoRaWAN™ version (by default) or Lora Ewattch version allowing measurement of currents up to 600A. KIT-SQUID : Kit including the SQUID V2 sensor and all necessary accessories: a power supply with rail din 230VAC-5VDC mounting (ref: ALIM-RAIL-5V) and
Description du produit
The SQUID V2 is a sensor equipped with 12 current measuring clamps, which sends the measured current values via a LoRaWAN or Lora Ewattch wireless link. The product sends consumption values in Ah (in orange on the graph below) of
Measurements
The sensor enables to make different measurements. Here below are the wiring methods for each one. The technical characteristics are described at the bottom of the documentation. Measurements of current: The measurement of current is carried out by means of the
Cleaning the product
The cleaning of the product should be done with a dry, soft and lint-free cloth. Remove embedded deposits with a slightly damp cloth. Do not use any cleaner, alcohol or thinner.
Power supply of the sensor
The product must be powered by a 24VDC power supply and provide a minimum current of 1A. Connect the cable marked power supply of the product to this power supply. The red wire on the 24V and the black wire
Configuration software
A configuration software is available for the product. This software enables you to configure and update the product. The procedure below describes how to connect to the product Implementation Power the Tyness Download the Tyness Configurator software. This software is
Technical Specifications
POWER SUPPLY Voltage : 24VDC +-5% Power : 1,2W Power cable length : 1 meter (39,07 inches) Power supply voltage Fluctuation : ±5% of rated voltage POWER CURRENT MEASUREMENTS BY OPENING PINS Maximum allowable current/sections : 10mm/75A, 16mm/100A, 24mm/300A, 36mm/600A Measurable circuit
Hazards and warnings
The manufacturer cannot be held responsible if the instructions in this manual are not followed. Any intervention on the product must be carried out by a qualified person. The product must be replaced by a qualified person. The device must be used in