Tyness configuration
In order to configure the Tyness, the Tyness Configurator Software must be used.
It is available at this address: http://www.ewattch.com/documentations-techniques/
Using the Tyness configurator, the Modbus extension board should be configured as follows:
- The Tyness must be configured as a Modbus slave
 - The Modbus baudrate, parity and stop bit must be configured identically to the configuration of the PLC
 - The Modbus address of the Tyness must be configured
 - The bus master to be selected is “Generecic master“
 - In the periodicity section, the time between two uploads to the cloud in minutes can be configured
 - In the table size section, the length of the uploaded Modbus table must be configured
 - Click on the write button to enter the configuration in the Tyness
 