Technical specifications
Dimensions:1 additional standard location for TynessConnectors:● 1 connector● 8 terminals type AVX series 9276 (2/10° to 8/10° - 24 to 18 AWG)● Rigid and flexible multi-strandsNumber of inputs:4 individually configurable inputs in 0-10V or 4-20mA with common mass in all of
Description and usage
REFERENCE: TYNESS-OPT-ANA The TYNESS-OPT-ANA board is an additional board comprising 4 analog inputs configurable in 0-10V and 4-20 mA with common mass. It enables to read the information coming from any sensor with an analog 0-10V and/or 4-20 mA output For example: an automaton,
Hazards and Warnings
Manufacturer is not responsible for user’s failure to comply with the instructions contained in this manual. Any service performed on this product must be completed by a qualified individual. Replacement of this product must be performed by a qualified individual. Failure to use
MBus protocol
Necessary prerequisites for compatibility between an Mbus meter and a Tyness opt Mbus card Water meter : The following information (VIF) must be found in the data available via a measurement data query. VIF code (Value information field) Description: volume Coding: E001 0nnn Range: 10(nnn-6) m3
Contact
13, Rue Maurice Jeandon88100 Saint-Dié des VosgesFRANCEsales@ewattch.fr www.ewattch.com
Payload descriptions
A Tyness fitted with an M-BUS board transmits its data in raw format on the different LoRaWAN networks. The section below shows you how to decode the frames (Payload) sent by the Tyness. The following table describes the encoding of the data in
Settings
The board is configured with the Tyness Configurator software. Always use the latest version of the Tyness Configurator and check that your Tyness has the latest version of the firmware. If necessary, carry out an update. Step 1 ● Click on “Config” of the
Implementation
Above all, the Tyness and the board must be disconnected. The board must be installed carefully and with precision of the connectors on the locations EXT.1 and/or EXT.2 of the Tyness. The M-Bus bus cable of the type standard telephone cable – jYStY
Technical specifications
Dimensions: 1 additional standard location for Tyness Connectors: ● 1 connector type WAGO series 2059 for the bus M-Bus (0.14 to 0.34 mm2- 26 to 22 AWG) ● 1 connector type WAGO series 2059 for the power supply (0.14 to 0.34 mm2- 26 to 22 AWG) ●
Usage
The board can be set up on:● the TYNESS ENERGY (1 location)● the TYNESS MODULAR (2 locations).The board comprises two terminal blocks of type WAGO series 2059.One terminal block for the M-Bus connection cable (a standardtelephone cable – jYStY Nx2x0.8