Environnement / Ambiance Lite

1.Hazards and Warnings #

Manufacturer cannot be held responsible for failure by user to comply with the instructions in this manual.
Any service performed on this product must be completed by a qualified individual.
Replacement of this product must be performed by a qualified individual.
Failure to use this equipment in accordance with the specifications in this documentation could lead to a hazard.
No parts in this device should be replaced or removed.
Disconnect all power supplies before servicing the equipment.

2.Certifications and Conformities #

CEM
  • EN 61000-6-2 : Immunity for industrial environments
  • EN 61000-6-3 : Emissions for residential environments
  • EN 55022 : Immunity IT equipment
Radio
  • EN 30022
Sécurité
  • EN 61010 :  Metering equipment

3.References #

AMBIANCE-LITE
ENVIRONNEMENT sensor measuring temperature and humidity, including lithium 3.6V batteries, and communicating via LoRaWAN™.

Accessories :
  • PILE-LITH-AA
    3.6V AA Lithium battery. Capacity 2.7 Ah
  • ALIM-RAIL-5V
    Power supply 230 VAC – 5 VDC. DIN RAIL mounting
  • ALIM-BLOC-5V
    Power supply 230 VAC – 5 VDC compatible with power socket
  • ALIM-12V-BLOC
    Power supply 230 VAC – 12 VDC compatible with power socket
Option : 
  • AMBIANCE-OPT-CO2 :
    Option including the CO2 module, AMBIANCE and ENVIRONNEMENT sensor modifications and a 12V DC 500mA power supply unit
  • AMB-ENV-OPT-ALIM-EXT :
    ENVIRONNEMENT modifications allowing the use of an external power supply from 5VDC to 12VDC

4.Product description #

The ENVIRONNEMENT is a complete LoRaWAN™ sensor that can measure three different things: temperature and humidity, and CO2 as an option.

This product can run on batteries, which allows for more flexibility in its positioning.
In order to measure CO2, an EE893 sensor made by E+E must be connected to the ENVIRONNEMENT.

Its measuring cell uses dual-wavelength E+E infrared technology NDIR, which compensates for the effects of aging, is particularly resistant to pollution and offers great long-term stability.

The Environnement sensor is configurable via its software (available on request): transmission periods, radio communication parameters, network status, sensor measurement.

Caution : Measuring CO2 requires the use of an external power supply and cannot be run on batteries.

5.Product installation #

Installation of the sensor

Mounting

This equipment can be mounted a variety of ways :

  • screwing to the wall
  • Option : using a double-sided adhesive

In order to make installation easier, you must remove the rear part of the chassis using a screwdriver.
The last step is to screw the chassis to the wall (or mount it using a double-sided adhesive) and reassemble the front part fixed to the rear part thus mounted

6.Radio communication #

The ENVIRONNEMENT periodically sens its sensor measurements via a LoRaWAN™ radio link.
In order to configure the ENVIRONNEMENT for a LoRaWAN™ network, the encrypted identification code indicated on each product (DevEUI) is required.

As well as the following two codes AppEUI and AppKey provided with your order

Network connection process
  • Our products try to connect to the network when they start.
  • If it does not work, they will retry every 24 hours until it works.
Periodique network reconnection
  • Our products restart a network connection procedure every 7 days.
    These reconnections improve security.
    Indeed, reconnection to the network renews the encryption keys.
Configuration of switches

Payload descriptions

The ENVIRONNEMENT sensor transmits its data in raw format on different public and private LoRaWAN™ networks. The section below shows you to decode the frames (PayLoad) sent by this sensor.

Periodic frames

The periodic frames contain the data measured by the sensor ENVIRONNEMENT.

Example of a periodic transmitted frame (HEXADECIMAL) :

0005 00 6A0B 04 60

Explanation of the frame structure :

Status frame

The status frames contain information about the sensor (battery level, firmware version..)

Example of a transmitted (HEXADECIMAL) status frame :

100A 0000020401 0405 083C00

Explanation of the frame structure :

7.Technical specifications #

POWER SUPPLY
  • Voltage : 3.6 VDC
  • Life span on battery powers : 5 years*
  • Voltage using external power : 5 to 12 VDC

 

MEASUREMENTS
Temperature measurement:

Temperature : -40 to 60℃                   Accuracy : 0,5℃

 

Relative humidity:

Humidity : 0 to 100%                            Accuracy : 2%

 

Warning: Measurements performed outside of recommended operating conditions as listed below can damage the product.

RADIO COMMUNICATION
LoRaWAN™:
  • Frequency : 868MHz
  • Unique serial number : yes
  • Maximum transmission power : 25mW
  • Communication range : up to15km in open areas**

 

*With one transmission per hour
**Depending on the environnement

 

 

ENVIRONMENTAL CONDITIONS
  • Area of application : Indoors
  • Operating temperature : from 5 to 60℃
  • Storage temperature : from -20℃ to +70℃
  • Operating humidity : de 10 to 80%, without condensation
  • Maximum altitude : 2000 m

 

 

PHYSICAL CHARACTERISTICS
  • Dimensions (H X L X D) : 86 x 86 x 25.5 mm
  • Chassis material : ABS
  • Weight : 80g (without batteries)
  • Protection rating : IP20

8.Contact #

13, Rue Maurice Jeandon
88100 Saint-Dié des Vosges
FRANCE
sales@ewattch.com
+33(0)3.29.57.75.97
www.ewattch.com