Ambiance LoRaWAN
1.Hazards and Warnings
Manufacturer cannot be held responsible for failure by user to comply with the instructions in this manual.
Any service perfore on this product must be completed by a qualified individual.
Replacement of this product must be performed by a qualified individual.
Failure to use this equipment in accordance with the specifications in this documentation could lead to a hazard.
No parts in this device should be replaced or removed.
Disconnect all power supplies before servicing the equipment.
2.Certifications and Conformities
CEM
- EN 61000-6-2 : Immunity for industrial environments
- EN 61000-6-3 : Emissions for residential environments
- EN 55022 : Immunity IT equipment
Radio
- EN 30022
Sécurité
- EN 61010 : Metering equipment
3.References
AMBIANCE-LORAWAN :
LoRaWAN™ AMBIANCE sensor measuring temperature, humidity, rate of presence, brightness and, in option, CO2.
Accessoires :
PILE-LITH-AA
3.6V AA Lithium battery. Capacity 2.7 Ah
ALIM-RAIL-5V
Power supply 230 VAC – 5VDC. DIN RAIL mounting
ALIM-BLOC-5V
Power supply 230 VAC – 5 VDC compatible with power socket
ALIM-12V-BLOC
Power supply 230 VAC – 12 VDC compatible with power socket
Options :
AMBIANCE-OPT-CO2 :
Option including the CO2 module, AMBIANCE sensor modifications and a 12 VDC 500mA power supply unit.
AMB-ENV-OPT-ALIM-EXT :
AMBIANCE modifications allowing the use of an external power supply from 5VDC to 12VDC
4.Product description
The AMBIANCE is a complète LoRaWAN™ sensor that can measure five different things: temperature, humidity, rate of presence, brightness, and CO2 as an option.
This product can run on batteries, which allows for more flexibility in its positioning.
In order to measure CO2, an EE893 sensor made by E+E must be connected to the AMBIANCE.
Its measuring cell uses dual-wavelength E+E infrared technology NDIR, which compensates for the effects of aging, is particularly resistant to pollution and offers great long-term stability.
The Ambiance sensor is configurable via its software (available here): transmission periods, radio communication parameters, network status, sensor measurement.
Caution : Measuring CO2 requires the use of an external power supply and cannot be run on batteries.
5.motion detection description
6.Product installation
Mise en place du capteur
Fixation
This equipment can be mounted a variety of ways :
- screwing to the wall
- Option : using a double-sided adhesive
In order to make installation easier, you must remove the rear part of the chassis using a screwdriver.
The last step is to screw the chassis to the wall (or mount it using a double-sided adhesive) and reassemble the front part fixed to the rear part thus mounted.
Description of sensor
7.Radio communication
The AMBIANCE periodically send its sensor measurements via a LoRaWAN™ radio link.
In order to configure the AMBIANCE sensor for a LoRaWAN™ network, the unique encrypted identification code indicated on each product (DevEUI) is required.
As well as the following two codes AppEUI and AppKey provided with your order.
Network connection process
- Our products try to connect to the network when they start
- If it does not work, they will retry every 24 hours until it works.
Periodique network reconnection
- Our products restart a network connection procedure every 7 days.
These reconnections improve security.
Indeed, reconnection to the network renews the encryption keys.
Configuration of switches
Payloads descriptions
The AMBIANCE sensor transmits its data in raw format on different public and private LoRaWAN™ networks. The section below shows you how to decode the frames (PayLoad) sent by the AMBIANCE.
Periodic frames :
The periodic frames contain the data measured by the AMBIANCE sensor.
Example of a periodic transmitted frames (HEXADECIMAL) :
000E 00 6A0B 04 60 08 A802 10 2E04 14 5000
Status frame
The status frame contain supplementary information about the sensors (battery level, firmware version, etc.)
Example of a transmitted (HEXADECIMAL) status frame :
100A 0002 020401 0407 083C00
Explanation of the frame structure :
8.Technical specifications
POWER SUPPLY
- Voltage : 3.6 VDC
- Life span on battery power : up to 5 years depending on use
- Voltage using external power : 5 to 12 VDC
MEASUREMENTS
Temperature measurement :
Temperature : -40 to 60℃ Accuracy : 0,3℃
Relative humidity :
Humidity : 0 to 100% Accuracy : 1%
Brightness measurement :
Brightness : 0 to 65535Lux Accuracy : 3Lux*
Measurement of CO2 level :
CO2 level : 0 to 10000PPM Accuracy : 100ppm + 5%
Presence measurement :
Presence measurement range : 5 to 6 m
Angle de détection : 130°
Warning: Measurements performed outside of recommended operating conditions as listed below can damage the product.
RADIO COMMUNICATION
LoRaWAN™:
- Frequency : 868MHz
- Unique serial number : yes
- Maximum transmission power : 25mW
- Communication range : up to 15km in open areas
ENVIRONMENTAL CONDITIONS
- Area of application : indoors
- Operating temperature : from 5 to 60°
- Storage temperature : from -20° to +70°
- Operating humidity : from 10 to 80%, without condensation
- Maximum altitude : 2000 m
- Power supply voltage fluctuation : ±10% of the nominal voltage
PHYSICAL CHARACTERISTICS
- Dimensions (H X L X P) : 86 x 86 x 25.5 mm
- Chassis material : ABS
- Weight : 80g (without batteries)
- Protection rating : IP20
9.Contact
13, Rue Maurice Jeandon
88100 Saint-Dié des Vosges
FRANCE
sales@ewattch.com
+33(0)3.29.57.75.97
www.ewattch.com